Permit: T07ME00303

Parcel: 135021270

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/14/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A TRAP ON CONDENSATE DRAIN. PROVIDE AN OVERFLOW SENSOR
2. GAS FLEX CANNOT EXCEED 3' IN LENGTH. PROVIDE A SEDIMENT TRAP
3. INSULATE SHEETMETAL SLEEVE
4. PROVIDE A FILTER GRILLE
5. CONNECT OVERFLOW SENSOR OR PUMP. PROVIDE HOSE CLAMPS
6. PROVIDE ROOF JACKS AT ELEC. PENETRATIONS

PROVIDE APPROVED FITTINGS
INSTALL CONDENSOR
07/17/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- THERE ARE TOO MANY CODE VIOLATIONS TO WRITE ON ONE PIECE OF PAPER
- WORK ON CONDENSOR -- NOT COMPLETE
- MECH. CONTRACTOR MUST BE HERE AT TIME OF INSPECTION
- PROVIDE A PERMIT & INSPECTION FOR NEW WATER HEATER
- BE SURE TO INCLUDE THE PETITION OF APPEAL FOR ALTERNATE METHOD OF T&P RELIEF DISCHARGE.