Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/21/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
VENTS ON DRAIN TRAPS SHOULD BE CHANGED ON EXISTING A/C UNITS. DRAIN PAN MAY NOT DRAIN PROPERLY.
06/08/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. VENT ON CONDENSATE DRAINS MUST BE DOWNSTREAM OF THE TRAP.
2. PROVIDE A GAS VALVE AT THE FLEX CONNECTOR
3. PERMANENT I.D UNITS
4. RELOCATE TRAP FROM 5 TON UNIT AHEAD OF ANY OTHER CONDENSATE CONNECTIONS. UNIT 8 IS NOW DOUBLE TRAPPED.