Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE VENTS ON DRAIN TRAPS SHOULD BE CHANGED ON EXISTING A/C UNITS. DRAIN PAN MAY NOT DRAIN PROPERLY. |
|
| 06/08/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. VENT ON CONDENSATE DRAINS MUST BE DOWNSTREAM OF THE TRAP. 2. PROVIDE A GAS VALVE AT THE FLEX CONNECTOR 3. PERMANENT I.D UNITS 4. RELOCATE TRAP FROM 5 TON UNIT AHEAD OF ANY OTHER CONDENSATE CONNECTIONS. UNIT 8 IS NOW DOUBLE TRAPPED. |