Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/03/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AN OVERFLOW SENSOR OR SECONDARY DRAIN OUTLET. 2. PROVIDE SEDIMENT TRAPS AT FURNACE & WATER HEATER 3. PROVIDE A PERMIT FOR NEW WATER HEATER & PROVIDE A PETITION OF APPEAL FOR ALTERNATE METHOD OF TERMINATING T&P RELIEF DRAIN. 4. T&P CANNOT RUN UPHILL 5. YOU CANNOT HAVE COPPER FLEX ON A T&P DRAIN. 6. SLOPE THE VENT CONNECTOR MIN. 1/4" PER FT & PROVIDE SCREWS. 7. PROVIDE PROPER DESCRIPTION OF WORK PERFORMED 8. A SPLIT SYSTEM WAS NOT REPLACED 9. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 10. SUPPORT COPPER DRAIN EVERY 6' |