Permit: T07ME00300

Parcel: 129065270


Addresses:

2944 E 21ST ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/04/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
05/25/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED SUPPLY DUCTS ON ROOF.
2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. PROVIDE A SERVICE RECEPTACLE ON ROOF W/GFI & WATERPROOF COVER.
3. CONDENSATE CANNOT DRIP ONTO THE DRIVEWAY - SUPPORT PVC EVERY 4'