Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00299
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
06/29/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FAILURE TO COMPLY WITH 5/7/07 INSPECTION NOTES WILL RESULT IN REFEE AT REINSPECTION |
|
05/07/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE THE PROPER DATA PLATE FOR THE HEAT STRIP INSTALLED. DO NOT LABEL ANYTHING OUTDOORS WITH INK. IF RHEEM CANNOT PROVIDE THE PROPER DATA PLATE, THEN DON'T USE A 5 KW HEAT STRIP. WHY DO YOU HAVE 50 AMP FUSES FOR A 5KW HEAT STRIP IN THE FIRST PLACE? WHAT SIZE DUCT LINER IS IN THE EXPOSED DUCT ON ROOF? 2" R8 IS REQUIRED. PROVIDE A SERVICE RECEPTACLE ASPER ARTICLE 210.63 N.E.C |