Permit: T07ME00298

Parcel: 133101730

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/25/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE LISTING ON INSULATION IN EXPOSED DUCT ON ROOF.
2. LOW VOLTAGE WIRE MUST BE PROTECTED FROM DAMAGE, USE CONDUIT IF NEEDED.
3. 3/8" I.D X 36" GAS FLEX NOT ADEQUATE FOR 80,000 BTU
4. SUPPORT ELEC. CONDUIT
5. PAINT EXPOSED PVC W/LATEX.
6. BLOCK & CLAMP EVERY 4'
7. ELEC. CIRCUIT ON SEPARATE PERMIT WITH PANEL UPGRADE
8. ADD GAS LINE TO MECH. PERMIT.
2. LOW VOLTAGE WIRE MUST BE PROTECTED FROM DAMAGE, USE CONDUIT IF NEEDED.
3. 3/8" I.D X 36" GAS FLEX NOT ADEQUATE FOR 80,000 BTU SUPPORT ELEC. CONDUIT.
4. PAINT EXPOSED PVC W/LATEX. BLOCK & CLAMP EVERY 4'
5.