Permit: T07ME00278

Parcel: 113082920


Addresses:

808 E HEDRICK DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/21/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS OK
04/26/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE APPLIANCE CONNECTOR & GAS SHUTOFF VALVE MUST BE CONNECTED AT THE APPLIANCE, NOT 5 OR 6' AWAY. PROVIDE A SEDIMENT TRAP AT CONNECTION TO THE APPLIANCE.
2. PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE UPPER ROOF. WHEN RUNNING A NEW CIRCUIT TO THE ROOF, YOU MUST ALSO PROVIDE A SERVICE RECEPTACLE AS PER N.E.C WITH A WATERPROOF COVER & GFI RECEPTACLE
3. CONDENSATE CANNOT DRIP ONTO A HARD SURFACE
CLAMP DRAIN LINE TO BLOCKS.