Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS OK |
|
| 04/26/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE APPLIANCE CONNECTOR & GAS SHUTOFF VALVE MUST BE CONNECTED AT THE APPLIANCE, NOT 5 OR 6' AWAY. PROVIDE A SEDIMENT TRAP AT CONNECTION TO THE APPLIANCE. 2. PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE UPPER ROOF. WHEN RUNNING A NEW CIRCUIT TO THE ROOF, YOU MUST ALSO PROVIDE A SERVICE RECEPTACLE AS PER N.E.C WITH A WATERPROOF COVER & GFI RECEPTACLE 3. CONDENSATE CANNOT DRIP ONTO A HARD SURFACE CLAMP DRAIN LINE TO BLOCKS. |