Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 05/11/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A RECEPTACLE FOR CONDENSATE PUMP 2) DO NOT CUT PLUG OFF OF CORD AND DO NOT EXTEND THE CORD WITH WIRE NOT CONNECTORS. RECOMMEND 120V PUMP 3) REPLACE FLAT CONDENSATE TRAP 4) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND-SUPPORT EVERY 6' 5) PROVIDE ELECTRIC UPGRADE PERMIT 6) PROVIDE A SERVICE RECEPTACLE ON ROOF |