Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/24/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. 40 AMP BKR. IN BOX AT UNIT - MAX. FUSE SIZE THIS UNIT
35 AMPS -- LEAVE PROPER SIZE PROTECTION AS NECESSARY.
2. CANNOT TERMINATE CONDENSATE DUMPING OFF FASCIA BOARD. TERMINATE 6" ABOVE GRD.