Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PERMANENTLY ID DATA PLATE W/PROPER HEAT STRIP & FUSE ACCORDINGLY AS NOTED ON PREVIOUS INSPECTION. BLOCK & CLAMP PVC EVERY 4' CLAMP PIPE TO THE HOUSE REMOVE THE OLD COOLER CIRCUIT ON TERMINATE ENDS OF WIRE WITH WIRE NUTS. |
|
| 04/26/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/18/2007 | MECHANICAL - FINAL | Denied | 1. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PAINT EXPOSED PVC W/LATEX PAINT 2. DISCONNECT IS OVERFUSED. PERMANENTLY I.D DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY 3. PROPERLY SECURE ELEC. CONDUITS PROVIDE A ROOF JACK AT ELEC. CONDUIT PENETRATION. TERMINATE OLD COOLER DISCONNECT WITH PROPER METHODS. 4. PROVIDE A PERMIT FOR NEW WATER HEATER |