Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 04/03/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A SECONDARY DRAIN TO A CONSPICUOUS LOCATION OR PROVIDE AN OVERFLOW SENSOR. 2. PROVIDE HOSE CLAMPS ON PUMP DRAIN CONNECTIONS 3. PROVIDE A ROMEX CONNECTOR WHERE POWER CORD CONNECTS TO FURNACE. 4. GAS FLEX CONNECTOR NOT ADEQUATE FOR 100,000 BTU FURNACE 5. INSULATE SHEET METAL DUCT ON TOP OF EVAP. COIL 6. DO NOT USE WHITE WIRE TO POWER CONDENSOR TAPE BOTH ENDS WITH BLACK TAPE. 7. 60 AMP CIRCUIT REQUIRES #6 WIRE --50 AMP YOU COULD USE #8 |