Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/03/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 1ST 15FT SECTION OF CONDENSATE DRAIN HAS NO SLOPE PAINT ALL EXPOSED PVC W/LATEX PAINT. TERMINATE CONDENSATE WITH AN ELBOW & NIPPLE & DIVERT WATER AWAY FROM HOUSE. 2. INSTALL COVER ON LB FITTING ON ROOF FOR LOW VOLTAGE WIRING. 3. HEAT STRIP NOT FUSED CORRECTLY FOR 240V 4. 60 AMP CIRCUITS REQUIRE #6 WIRE 5. WAS 2" R8 DUCT LINE USED IN THE SUPPLY DUCT ON THE ROOF AS REQUIRED BY THE I.E.C.C? |