Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/20/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO FINAL INSPECTION UNTIL REFEE IS PAID |
|
| 04/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR TO PAY REFEE FOR NOT COMPLYING WITH ALL NOTES ABOVE. THERE WAS NO MESSAGE LEFT TO RETRIEVE HAVE LADDER ON SITE TO PROVIDE ACCESS. |
|
| 03/16/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROOFTOP DISCONNECT SHALL BE MADE UP WITH ALL WIRES UNDER LUGS AND PROPERLY CLOSE TO BE WATER RESISITANT 2. WHITE WIRES TO BE TAPPED BLACK. 3. PROVIDE CORRECT SEPARATION DAMPERS FOR AC/MASTER COOL UNIT. 4. CONTRACTOR TO MEET INSPECTOR ON SITE FOR MINIMUM SOAP TEST ON ADDITIONAL GAS PIPING. |