Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 06/20/2007 | MECHANICAL - FINAL | Cancelled | IVRS - RI canceled | |
| 04/04/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ALL ON ROOF OKAY UNIT "D" OKAY NO ACCESS TO UNIT "A" |
|
| 03/26/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT D: PROVIDE A SECONDARY DRAIN OR A OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET. IF PIPING, THE SECONDARY MUST TERMINATE TO A CONSPICOUS LOCATION TIGHTEN ROMEX CONNECTOR ONTO POWER CORD SECURE DRAIN LINE FROM PUMP IN CLOSET -------------------------------------------------------------------------------------------------UNIT A & D: SUPPORT LINE SET ON ROOF AND ELECTRIC CONDUIT CONDENSATE CANNOT TERMINATE INTO A SEWER VENT DO NOT USE WHITE WIRE TO POWER THE CONDENSOR PULL A NEW WIRE TO REPLACE THE WHITE WIRE NO BLACK TAPE ON ENDS UNLESS ROMEX WAS USED NEED ACCESS TO UNIT A FOR FURNACE INSPECTION |