Permit: T07ME00145

Parcel: 11106384A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/21/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
06/20/2007 MECHANICAL - FINAL Cancelled IVRS - RI canceled
04/04/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ALL ON ROOF OKAY
UNIT "D" OKAY
NO ACCESS TO UNIT "A"
03/26/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT D:
PROVIDE A SECONDARY DRAIN OR A OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET. IF PIPING, THE SECONDARY MUST TERMINATE TO A CONSPICOUS LOCATION
TIGHTEN ROMEX CONNECTOR ONTO POWER CORD
SECURE DRAIN LINE FROM PUMP IN CLOSET
-------------------------------------------------------------------------------------------------UNIT A & D:
SUPPORT LINE SET ON ROOF AND ELECTRIC CONDUIT
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
DO NOT USE WHITE WIRE TO POWER THE CONDENSOR
PULL A NEW WIRE TO REPLACE THE WHITE WIRE
NO BLACK TAPE ON ENDS UNLESS ROMEX WAS USED
NEED ACCESS TO UNIT A FOR FURNACE INSPECTION