Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00135
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
04/06/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONDENSATE PUMPED DRAIN PIPING SHALL TERMINATE AT AN APPROVED RECEPTOR OR GROUND LEVEL IN AN AREAS WHICH CAN ABSORB MOISTURE. SHALL NOT TERMINATE AT VENT ON ROOF 2) CONDENSATE DRAIN PIPING TO BE SUPPORTED AND SECURED AT 6' INTERVALS |