Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/23/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE DRAIN HAS NEGATIVE PITCH AT WEST END
03/12/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINE. SEAL HOLES IN DUCT WORK. RECALL FOR INSPECTION.