Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HUMIDIFIER CONTROL WIRING TO BE PROTECTED FROM WEATHER & VERMIN 2. CONDENSATE DRAIN TO BE ON SUPPORTS ON ROOF AT 4' INTERVALS 3. PROVIDE CORRECT PERM CAP OR TRANSITION FITTING FOR VENT SYSTEM FROM WATER HEATER TO DOUBLE WALL VENT AT CEILING ELEVATION. 4. PROVIDE 3-GALV SCREWS AT EACH JOINT OF VENT PIPING AND PROVIDE APPROVED SINGLE WALL VENT PIPING FROM WATER HEATER. |