Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE LOOSE PIECE OF INSULATION IN SUPPLY TO DINING AREA. REMOVE ALL EXPOSED DUCT FROM ROOF & RE-INSULATE WITH R8 DUCT LINER OR INSULATE OUTSIDE OF EXISTING DUCT & COVER WITH WATERPROOF MATERIAL. RESIZE DUCT AS NEEDED. |
|
| 02/23/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 120,000 BTU 2. #8 WIRE NOT ADEQUATE FOR 60 AMP SERVICE 3. EXPOSED SUPPLY DUCT ON ROOF MUST BE INSULATED WITH SUPPLY. MIN. 2" - R8 DUCT LINER. ALL LEADING EDGES MUST BE COVERED WITH SHEETMETAL. BE SURE TO GLUE & PIN ALL INSULATION. |