Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00063
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
02/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A BUSHING IN ELECTRIC DISCONNECT 2) DATA PLATE IS DAMAGED 3) CANNOT CONFIRM MAX FUSE SIZE 4) PROVIDE A NEW LABEL 5) PROVIDE A FRESH AIR INTAKE 6) PROVIDE 2" R-8 DUCT LINER IN EXPOSED DUCT ON ROOF 7) PROVIDE ACCESS INSIDE BLDG. NEED TO SEE CIRCUIT BREAKER AND ROOF JOISTS. BE SURE REDWOOD IS SPANNING ACROSS THE JOISTS |