Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
| 02/09/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT CANNOT LAY ON THE GROUND. STRAP ALL DUCTS EVERY 5' DUCT MUST BE MIN. 4" ABOVE THE GROUND INSULATE ALL SHEET METAL FITTINGS 2. PROVIDE A SEDIMENT TRAP AT GAS CONNECTION TO UNIT. |