Permit: T07ME00022

Parcel: 113101020

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/14/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
02/09/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE 1/8" PER FOOT SLOPE ON CONDENSATE
2. CONDENSATE TERMINATING AT GAS METER LOCATION IS NOT A GOOD IDEA.
3. INSTALL SEDIMENT TRAPS ON GAS SUPPLY.

PLEASE ASK OWNER TO ADDRESS THESE SAFETY CONCERNS.
PLEASE INSTALL PLUG IN OPEN SEWER AN HOSE BIB VACUUM BREAKERS ON UNINSPECTED WATER REPIPE.