Permit: T07ME00005

Parcel: 12107043A


Addresses:

6031 E BELLEVUE ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
02/01/2007 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
01/24/2007 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE APPROVED TAPE PRIMER & TAPE ON ALL BURIED FITTINGS & TOOL MARKS.
2. 10 PSI TEST IS OK - LEFT GAS CARD
3. PROVIDE SCREWS AT WATER VENT CONNECTION TO THE DRAFT DIVERTER.
4. INSULATE EXPOSED SUPPLY DUCT ON ROOF WITH 2" R-8 DUCT LINER. 1" LINER IS ONLY R4.2 SEE 2003 I.E.C.C
01/19/2007 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THIS IS ALSO A GAS REPIPE
2. EXPOSE NEW BELOW GRADE GAS PIPING - MUST HAVE FACTORY COATING.
3. PROVIDE 3/4" PIPING TO BE AS CLOSE TO GAS PACK AS POSSIBLE.
4. SECURE GAS PIPING DROP TO WH, INSTALL SEDIMENT TRAP AT WH
5. PROVIDE 1" CLEARANCE AT WH FLUE PENETRATION OF ROOF.