Case: T07FR02620

Parcel: 141153540

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR02620

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2008 INSP - FULL Approved
12/27/2007 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Fire extingushers have not been inspected in 2 years. They must be serviced yearly.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: Have fire extinguishers serviced and display a tag indicating so.

___2. PROBLEM: Extension cord connected to light behind T.V. in back room. Extension cord used with power strip under computer desk.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. AND: 605.4.2 Power supply. Relocatable power taps shall be
directly connected to a permanently installed receptacle.
REQUIRED CORRECTION: Light shall be plugged directly into power outlet or into a UL approved power strip. Power strip under computer shall be plugged directly into power outlet.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved