Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR02554
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
12/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.3 REMOVE ITEMS AROUND ELECTRICAL PANELS IN FAX MACHINE ROOM. KEEP ELECTRICAL ROOM CLEARED OF ALL ITEMS BY THE MAIN GATE. B BUILDING UPSTAIRS ELECTRICAL ROOM BY ELEVATOR REMOVE ALL ITEMS INSIDE. B BUILDING DOWNSTAIRS REMOVE ALL ITEMS FROM ELECTRICAL ROOM |
|
12/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.3.1 SIGN "ELECTRICAL ROOM" BY MAIN GATE WITH 2" LETTERS. SIGN "ELECTRICAL ROOM" BY ELEVATOR UPSTAIRS (B BLD) SIGN "ELECTRICAL ROOM" DOWN STAIRS (B BLD) |
|
12/19/2007 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.4 INSTALL SURGE PROTECTOR IN CAREER DEV (LISA) ROOM. |