Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR02551

Parcel: 13348128C


Addresses:

30 S HOUGHTON RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR02551

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2008 VIOL - FIRE PROTECTION SYSTEMS Approved Conditions 2 and 3 abated. Regarding manual activation pull stations being too close: Per Chief Uthe suppression hood systems will not have to be updated until such a time as service or hydrostatic testing requires upgrade to UL 300 system. This inspector strongly recommended to manager that pull stations be moved per current code for employee safety.
02/14/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
12/18/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required The Tucson Fire Department has conducted a hood suppression system inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Manual activation pull stations are too close to cooking appliance and are blocked from access.
TFC REFERENCE: 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximumof
20 feet (6096 mm) from the kitchen exhaust system.
The manual actuation device shall be installed not more than
48 inches (1200 mm) nor less than 42 inches (1067 mm)
above the floor and shall clearly identify the hazard protected.
The manual actuation shall require a maximum force
of 40 pounds (178 N) and a maximum movement of 14
inches (356 mm) to actuate the fire suppression system.
REQUIRED CORRECTION: Have qualified individual install manual activation device as per code. Manual activation device must not be blocked from access.

___2. PROBLEM: Red caps missing from nozzle tips. These caps are necessary to keep nozzle tips from becoming obstructed or clogged with grease build up.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. AND: NFPA 17A, 4.3.1.5: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture or other foreign materials into the piping.
REQUIRED CORRECTION: Nozzle tips shall be free of obstructions and capped.

___3. PROBLEM: Service records not available on the premises for inspection.
TFC REFERENCE: 901.6.2 Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
REQUIRED CORRECTION: Have copies of service and maintenance records available on the premises for the fire code official to inspect.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

___Approved

___Not Approved