Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR02509

Parcel: 141153570

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR02509

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2008 INSP - FULL Approved
12/10/2007 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: FDC missing cap.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: Have sprinkler service company replace missing cap on FDC.

___2. PROBLEM: Opening in ceiling in storage room.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire.
REQUIRED CORRECTION: Replace missing drop ceiling panel in storage room.

___3. PROBLEM: Electrical equipment room not labeled.
TFC REFERENCE: 608.7.1 Equipment room and building signage. Doors into electrical equipment rooms or buildings containing stationary battery systems shall be provided with approved
signs.
REQUIRED CORRECTION: Affix sign to electrical equioment room indicating Electrical Equipment.

RECOMMENDATION: Install a knox box key box outside sprinkler riser room so TFD has access to sprinkler equipment in a timely fashion.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.


Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved