Case: T07FR02506

Parcel: 12601003C

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR02506

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2007 VIOL - MEANS OF EGRESS Approved All abated- Good Job!!
12/10/2007 VIOL - MEANS OF EGRESS Violation Blocked exit:

1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way.
12/10/2007 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:

IFC2006 [TFC with modifications] / 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove keyed dead bolt. Replace with thumb turn bolt, and this MUST be unlocked during business hours and while occupied by the public.
12/10/2007 VIOL - MEANS OF EGRESS Violation Exit signs:

IFC2006 [TFC with modifications] / 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

______Place exit signs in an approved manner over the back hallway pointing the way to the door, and one over the rear door.


Re-inspection date scheduled on or after Dec. 31, 2007.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________I have received a copy of this inspection report.
Building Representative


_____________________________________________
Captain