Case: T07FR02506

Parcel: 12601003C

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR02506

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

IFC2006 [TFC with modifications] / 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strip. [Refrigerator]
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

IFC2006 [TFC with modifications] / 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Blocked electrical panel:

IFC 2006 with modifications 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.

______Clear area in front of electrical panel in an approved manner.