Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | INSP - FULL | Approved | All violations corrected | |
| 12/05/2007 | INSP - FULL | Correction Required | 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. ___ Remove obstructions from both double doors and patio gates. Path of egress is not to be narrower than doorway and gates are to be in fully open position. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ___ Have extinguishers inspected or removed from facility. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. ___ Keep access to all extinguishers clear. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ___ Hang all extinguishers from brackets or install cabinets |
|
| 12/03/2007 | INSP - FULL | Correction Required | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. ___ Plug powerstrip in upstairs office directly into outlet. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ___ Replace electrical box cover by roll-up door. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ___ Label riser room. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 508.5.4 Obstruction. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment... ___Remove or organize storage in riser room. |
|
| 12/03/2007 | INSP - FULL | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. ___ Post sign over all doors. (Southeast door may have one-sided lock installed) |
|
| 12/03/2007 | INSP - FULL | Correction Required | No Certificate of Occupancy |