Case: T07FR02445

Parcel: 11706320C


Addresses:

330 S TOOLE AV


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR02445

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
12/20/2007 VIOL - FIRE PROTECTION SYSTEMS Approved All corrected.
12/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

___ Have all required extinguishers inspected.

___ Remove non-inspected extinguishers.

___ Provide copy of annual sprinkler system inspection.
12/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.

___ Repair holes in closet in women's bathroom.
12/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1008.1.8.3 Locks and latches
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background

___ Provide sign over southeast doors.
12/03/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

___Remove bolt lock from upstairs exit.