Case: T07FR02431

Parcel: 136313180

Inspection Status: Approved

Inspection History: INSP - AST/UST

Date Description Inspector Results Comments
03/31/2008 INSP - AST/UST Approved Completed final inspection. No leaks detected. All emergency stops tested and are functional. Approved for dispensing.
03/13/2008 INSP - AST/UST Continued Witnessed the installation of flex connections to the vent pipes
01/14/2008 INSP - AST/UST Continued Performed piping pressure and soap test. approved
11/28/2007 INSP - AST/UST Continued Installed two 20,000 Glasssteel II tanks. Both arrived under vacuum. Vacuum was checked after back filling and remained at 12 and 14 PSI.
11/27/2007 INSP - AST/UST Continued Inspected the pre-burial hole for the tanks. Gravel was 18 inches deep.