Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2007 | INSP - FULL | Approved | ||
| 11/21/2007 | INSP - FULL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Emergency lighting in front and back exit are nonfunctioning. TFC REF: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. REQUIRED CORRECTION: All emergency back up lighting units shall function properly. Additionally recommend emergency back up lighting units be tested every 3 months and repaired as necessary. ___2. PROBLEM: Extension cord under front desk in lobby. TFC REF: 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. REQUIRED CORRECTION: Replace extension cord with UL approved power strip or plug appliance directly into outlet. Property Representative signature:_________________________ Fire Inspector Signature:_________________________ 791-4502 Reinspection Date:___/___/___ _X__Approved ___Not Approved |