Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR02385

Parcel: 14042072A


Addresses:

7060 S TUCSON BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T07FR02385

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
11/20/2007 INSP - FULL Violation
11/20/2007 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
Tag all fire extinguishers.
11/20/2007 INSP - FULL Violation SECTION 703
FIRE-RESISTANCE-RATED CONSTRUCTION
703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
703.2 Opening protectives. Opening protectives shall be
maintained in an operative condition in accordance with NFPA
80. Fire doors and smoke barrier doors shall not be blocked or
obstructed or otherwise made inoperable. Fusible links shall be
replaced promptly whenever fused or damaged. Fire door assemblies
shall not be modified.
Seal all holes in sheetrock.Phone data room, 2nd floor storage main bldg. Banquet closet
11/20/2007 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
Remove any items 18 inches from celling.
11/20/2007 INSP - FULL Violation 407.1 General. The provisions of Sections 407.2 through
407.7 shall be applicable where hazardous materials subject to
permits under Section 2701.5 are located on the premises or
where required by the fire code official.
407.2 Material Safety Data Sheets. Material Safety Data
Sheets (MSDS) for all hazardous materials shall be readily
available on the premises.
407.3 Identification. Individual containers of hazardous materials,
cartons or packages shall be marked or labeled in accordance
with applicable federal regulations. Buildings, rooms
and spaces containing hazardous materials shall be identified
by hazard warning signs in accordance with Section 2703.5.
407.4 Training. Persons responsible for the operation of areas
in which hazardous materials are stored, dispensed, handled or
used shall be familiar with the chemical nature of the materials
and the appropriate mitigating actions necessary in the event of
a fire, leak or spill. Responsible persons shall be designated and
trained to be liaison personnel for the Fire Department. These
persons shall aid the Fire Department in preplanning emergency
responses and identification of the locations where hazardous
materials are located, and shall have access to Material
Safety Data Sheets and be knowledgeable in the site emergency
response procedures.
407.5 Hazardous Materials Inventory Statement. Where required
by the fire code official, each application for a permit
shall include a Hazardous Materials Inventory Statement
(HMIS) in accordance with Section 2701.5.2.
MSDS shall be available at front desk. All employees shall know where they are.
11/20/2007 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adaptors, such as cube
adaptors, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed.
605.4.2 Power supply. Relocatable power taps shall be directly
connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
Do not piggy back strip plugs.
11/20/2007 INSP - FULL Violation 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
605.2 Illumination. Illumination shall be provided for service
equipment areas, motor control centers and electrical
panelboards.
605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Put plates on recepticles.