Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2008 | VIOL - MEANS OF EGRESS | Approved | ||
| 12/14/2007 | VIOL - MEANS OF EGRESS | Partial Approval | Activity room still needs exit sign lit | |
| 11/06/2007 | VIOL - MEANS OF EGRESS | Violation | Throw bolt on kitchen door: IFC2006 [TFC with modifications] / 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove bolt latch from kitchen door. |
|
| 11/06/2007 | VIOL - MEANS OF EGRESS | Violation | Exit sign not lit: IFC2006 [TFC with modifications] / 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit sign. Re-inspection date scheduled on or after Nov. 26, 2007. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |