Case: T07FR02251

Parcel: 141185830

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/19/2007 INSP - FULL Approved Upon reinspection all violations corrected
11/05/2007 INSP - FULL Approved PROBLEM: Front exit sign indicating exit is to remain unlocked is partially blocked.
CODE REF: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
REQUIRED ACTION: Entire sign must be exposed.
11/05/2007 INSP - FULL Approved PROBLEM: No bracket for fire ext. Fire ext. last checked in 2003.
CODE REF: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or repaired where defective. AND: 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets.
REQUIRED ACTION: Have fire extinguisher mounted on a bracket and have it inspected and maintained at regular intervals.
11/05/2007 INSP - FULL Approved PROBLEM: Access to electrical panel blocked.
CODE REF: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment.
REQUIRED ACTION: Keep access to electrical panel clear.