Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2007 | INSP - FULL | Approved | Upon reinspection all violations corrected | |
| 11/05/2007 | INSP - FULL | Approved | PROBLEM: Front exit sign indicating exit is to remain unlocked is partially blocked. CODE REF: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, REQUIRED ACTION: Entire sign must be exposed. |
|
| 11/05/2007 | INSP - FULL | Approved | PROBLEM: No bracket for fire ext. Fire ext. last checked in 2003. CODE REF: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. AND: 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets. REQUIRED ACTION: Have fire extinguisher mounted on a bracket and have it inspected and maintained at regular intervals. |
|
| 11/05/2007 | INSP - FULL | Approved | PROBLEM: Access to electrical panel blocked. CODE REF: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. REQUIRED ACTION: Keep access to electrical panel clear. Inspector Signature:____________________ Property Representative Signature:____________________ |