Case: T07FR02250

Parcel: 141185830

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/19/2007 INSP - FULL Approved Upon reinspection all violations corrected.
11/05/2007 INSP - FULL Correction Required FIRE INSPECTION REPORT
A/P/D: T07FR02250

November 5/2007

Long Realty
ATTN: Malissa Brown
10222 E Rita Rd.
Tucson, AZ. 85747


Mrs. Brown,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on November 5, 2007. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). A Re-inspection will be performed on or about November 19, 2007

Notice of Violations:
_____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
· Fire extinguisher shall be serviced annually (last inspection 2003).


_____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied. Provide back up power supply for all required exit illumination:
· Exit sign and emergency backup lighting in the break room shall operate


_____ 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever
the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards.
· Replace missing escheson in the ladies bathroom.
· Re-adjust sprinkler head in the ladies bathroom so that the coverage is not hampered.
· Extend sprinkler system to maintain coverage in the "West Wing" bathroom
-Currently there is no cover in the room



The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated.

__________________________________________________
Property owner or Property Representative Signature
_________________________________
Abatement Date
__________________________
Captain Signature


Sincerely,


Jimmy R. Davis, Jr
Fire Inspector
Tucson Fire Department