Inspection History Details
Inspection Status: Approved
Inspection History: COMPL - INITIAL INSPECTION
Case Number - T07FR02231
Inspection Description - COMPL - INITIAL INSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2007 | COMPL - INITIAL INSPECTION | Approved | Upon reinspection, all violations corrected. Inspection approved | |
11/19/2007 | COMPL - INITIAL INSPECTION | Approved | Upon Reinspection on 11/15/07 the following problems that need correcting were found: ___1. PROBLEM: Double bolt lock on back door TFC REF: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. REQUIRED CORRECTION: Replace double key bolt lock with thumb turn lock on back warehouse door. ___2. PROBLEM: Sprinkler valve not secured open TFC REF: As required in NFPA 25, section 13.3.1.3: "Each normally open valve shall be secured by means of a seal or a lock or shall be electrically supervised..." REQUIRED CORRECTION: Chain and lock the control valve on the sprinkler system in the open position. Notify and provide a key for the personnel who maintain and inspect your system. ___3. PROBLEM: Emergency lighting in warehouse not working. TFC REF: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. REQUIRED CORRECTION: All emergency backup units shall function properly. Also as per above recommendation: Test emergency backup lighting and lighted exit signs every 3 months and replace bulbs and or batteries as necesssary. Property Representative Signature_________________________ Inspector Signature: _________________________ Reinspection date: ___/___/___ |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 2. Extension cord: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Required action: lamp by fountain on back wall of show room to be plugged into outlet or power strip. |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 3. Clearance in front of electrical panel in warehouse area: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Required Action: Clear furniture and other obstructions from around electrical panel to required distances. |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 4. Sprinkler Riser area clutter. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. Required Action: Remove clutter, buckets etc from around sprinkler riser to a distance of at least 30 inches |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 5. Identification of sprinkler riser room: Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | Recommendation: Install a lock box key box: 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. |
|
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | Recommendation: Test emergency back up lighting and lighted exit sign every 3 months and replace light bulbs as necessary. | |
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 6. Certificate of Occupancy: Have a copy of the certificate of occupancy readily available on the premises; IBC 105.1 | |
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 1. 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted... Required action: Clear path to exit toward SW exit to 36 inches in width. | |
10/30/2007 | COMPL - INITIAL INSPECTION | Approved | 6. Exit door to outside in warehouse: 1008.1.8.3 the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. Required Action: Affix required sign as specified. |