Case: T07FR02231

Parcel: 133233570


Addresses:

7671 E BROADWAY BL


Inspection Status: Approved

Inspection History: COMPL - INITIAL INSPECTION

Case Number - T07FR02231

Inspection Description - COMPL - INITIAL INSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2007 COMPL - INITIAL INSPECTION Approved Upon reinspection, all violations corrected. Inspection approved
11/19/2007 COMPL - INITIAL INSPECTION Approved Upon Reinspection on 11/15/07 the following problems that need correcting were found:

___1. PROBLEM: Double bolt lock on back door
TFC REF: 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
REQUIRED CORRECTION: Replace double key bolt lock with thumb turn lock on back warehouse door.

___2. PROBLEM: Sprinkler valve not secured open
TFC REF: As required in NFPA 25, section 13.3.1.3: "Each normally open valve shall be secured by means of a seal or a lock or shall be electrically supervised..."
REQUIRED CORRECTION: Chain and lock the control valve on the sprinkler system in the open position. Notify and provide a key for the personnel who maintain and inspect your system.

___3. PROBLEM: Emergency lighting in warehouse not working.
TFC REF: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: All emergency backup units shall function properly. Also as per above recommendation: Test emergency backup lighting and lighted exit signs every 3 months and replace bulbs and or batteries as necesssary.


Property Representative Signature_________________________

Inspector Signature: _________________________


Reinspection date: ___/___/___
10/30/2007 COMPL - INITIAL INSPECTION Approved 2. Extension cord: 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Required action: lamp by fountain on back wall of show room to be plugged into outlet or power strip.
10/30/2007 COMPL - INITIAL INSPECTION Approved 3. Clearance in front of electrical panel in warehouse area: 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Required Action: Clear furniture and other obstructions from around electrical panel to required distances.
10/30/2007 COMPL - INITIAL INSPECTION Approved 4. Sprinkler Riser area clutter. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection
equipment or fire hydrants. Required Action: Remove clutter, buckets etc from around sprinkler riser to a distance of at least 30 inches
10/30/2007 COMPL - INITIAL INSPECTION Approved 5. Identification of sprinkler riser room: Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.
10/30/2007 COMPL - INITIAL INSPECTION Approved Recommendation: Install a lock box key box: 506.1 Where required. Where access to or within a structure
or an area is restricted because of secured openings or where
immediate access is necessary for life-saving or fire-fighting
purposes, the fire code official is authorized to require a key
box to be installed in an approved location. The key box shall
be of an approved type and shall contain keys to gain necessary
access as required by the fire code official.
10/30/2007 COMPL - INITIAL INSPECTION Approved Recommendation: Test emergency back up lighting and lighted exit sign every 3 months and replace light bulbs as necessary.
10/30/2007 COMPL - INITIAL INSPECTION Approved 6. Certificate of Occupancy: Have a copy of the certificate of occupancy readily available on the premises; IBC 105.1
10/30/2007 COMPL - INITIAL INSPECTION Approved 1. 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted... Required action: Clear path to exit toward SW exit to 36 inches in width.
10/30/2007 COMPL - INITIAL INSPECTION Approved 6. Exit door to outside in warehouse: 1008.1.8.3 the main exterior door or doors are permitted to be equipped
with key-operated locking devices from the egress
side provided: 2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background. Required Action: Affix required sign as specified.