Case: T07FR02217

Parcel: 13804180C


Addresses:

617 W VALENCIA RD


Inspection Status: Approved

Inspection History: INSP - AST/UST

Case Number - T07FR02217

Inspection Description - INSP - AST/UST

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2007 INSP - AST/UST Approved Vents have been installed on the tank and it has been moved away from the exit
10/29/2007 INSP - AST/UST Approved 3404.2.7.3.3 - Vent pipe outlets: Vent outlets
on atmospheric tanks storing Class IIIB liquids are
allowed to discharge inside a building if the vent is a normally closed vent.
10/29/2007 INSP - AST/UST Approved 3404.2.7.4 - Emergency Venting: Stationary,
above-ground tanks shall be equipped with additional
venting that will relieve excessive internal pressure
caused by exposure to fires.
10/29/2007 INSP - AST/UST Approved 3404.3.3.3 - Clear means of egress: Storage of any liquids,
including stock for sale, shall not be stored within 10 feet of an exit door or
be allowed to obstruct physically the route of egress.