Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST/UST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/26/2007 | INSP - AST/UST | Approved | Vents have been installed on the tank and it has been moved away from the exit | |
| 10/29/2007 | INSP - AST/UST | Approved | 3404.2.7.3.3 - Vent pipe outlets: Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. |
|
| 10/29/2007 | INSP - AST/UST | Approved | 3404.2.7.4 - Emergency Venting: Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. |
|
| 10/29/2007 | INSP - AST/UST | Approved | 3404.3.3.3 - Clear means of egress: Storage of any liquids, including stock for sale, shall not be stored within 10 feet of an exit door or be allowed to obstruct physically the route of egress. |