Case: T07FR02210

Parcel: 140420760

Inspection Status: Approved

Inspection History: VIOL - FIRE RESIST.RATED CONST

Date Description Inspector Results Comments
12/10/2007 VIOL - FIRE RESIST.RATED CONST Approved ALL OK
10/29/2007 VIOL - FIRE RESIST.RATED CONST Correction Required 704.2 Floor Openings and Shafts. When openings are required to be protected, opening protectives shall be maintained self-closing or automatic-closing by smoke detection.
· Adjust or install self-closing hinges
10/29/2007 VIOL - FIRE RESIST.RATED CONST Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
· Fill gaps in riser room and electrical room with UL fire-rated sealant
· Replace missing ceiling tile in electrical room