Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE RESIST.RATED CONST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2007 | VIOL - FIRE RESIST.RATED CONST | Approved | ALL OK | |
| 10/29/2007 | VIOL - FIRE RESIST.RATED CONST | Correction Required | 704.2 Floor Openings and Shafts. When openings are required to be protected, opening protectives shall be maintained self-closing or automatic-closing by smoke detection. · Adjust or install self-closing hinges |
|
| 10/29/2007 | VIOL - FIRE RESIST.RATED CONST | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. · Fill gaps in riser room and electrical room with UL fire-rated sealant · Replace missing ceiling tile in electrical room |