Case: T07FR02210

Parcel: 140420760

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
12/10/2007 VIOL - BUILDING SVCS & SYSTEMS Approved ALL OK
10/29/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 604.3.2 Written record. Written records of the inspection, testing and maintenance of emergency and standby power systems… shall be kept on the premises… and be available for inspection by the fire code official.
· Provide record of inspection/testing of emergency generator
10/29/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved working.
· Label electrical rooms and annunciator panel room
10/29/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
· Plug taps directly into receptacle
10/29/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
· In office, plug refrigerator directly into receptacle