Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ALL OK | |
| 10/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 604.3.2 Written record. Written records of the inspection, testing and maintenance of emergency and standby power systems… shall be kept on the premises… and be available for inspection by the fire code official. · Provide record of inspection/testing of emergency generator |
|
| 10/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved working. · Label electrical rooms and annunciator panel room |
|
| 10/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. · Plug taps directly into receptacle |
|
| 10/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. · In office, plug refrigerator directly into receptacle |