Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE SERVICE FEATURES
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2007 | VIOL - FIRE SERVICE FEATURES | Approved | ALL OK | |
| 10/29/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | 506.1 Key Boxes where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. · Provide key box near main entrance with building key. |
|
| 10/29/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for… sprinkler risers and valves… shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. · Label or provide signage for riser room door and annunciator panel room |
|
| 10/29/2007 | VIOL - FIRE SERVICE FEATURES | Correction Required | 507.2.2 Interior access to shaftways. Door or window openings to a hoistway or shaftway from the interior of the building shall be plainly marked with the word SHAFTWAY in red letters at least 6 inches hish on a white background. · Label doors to shaftways |