Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 901.6 #1.Properly align hood extinguishing system nozzles over cooking equipment. #2.Hood extinguishing systems shall be inspected, serviced and taged every 6 months. Provide documentation of current inspection. |
|
| 10/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | TFC 904.11.5 A class K rated fire extinguisher shall be provided within a 30 foot travel distance of commercial type cooking equipment. |