10/25/2007 INSP - FULL Violation On 9-25-07 and 10-24-07, a fire prevention inspection was conducted Armory Park Apartments, 211 South Fifth Ave. Tucson, and Arizona

The following Tucson Fire Code Violation(s) was noted:

1). Fire sprinkler test and inspection report due. : Last date March 2006
2). Fire alarm test report due. Last date March 2006
3). Fire alarm test report due. Last 2006
4). Currently door closures are not working in the following laundry rooms 8th, 7th, 3rd, and 2nd floor. These shall be repaired. IFC 703.2.2
5).
The following apartments are in violation of the fire code.
405: sprinkler head dusty, exit obstructions, too many combustible items, boxes, paper, plastics, it seems there is only 4 feet throughout apt. to exit from.
810" storage shall be 2 feet from ceiling in closet
807: new smoke detector needed
833: repair ceiling

This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 11-14-07 .
A re-inspection shall be conducted at that time to ensure compliance.