Case: T07FR02009

Parcel: 14042029A


Addresses:

7001 S TUCSON BL

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/09/2007 INSP - FULL Correction Required Fix all fire code violations.
10/09/2007 INSP - FULL Approved
10/09/2007 INSP - FULL Violation I.F.C. 2006, FIRE-RESISTANCE-RATED CONSTRUCTION
703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, fire stops,
shaft enclosures, partitions and floors) shall be maintained.
Such elements shall be properly repaired, restored or replaced
when damaged, altered, breached or penetrated. Openings
made therein for the passage of pipes, electrical conduit, wires,
ducts, air transfer openings, and holes made for any reason
shall be protected with approved methods capable of resisting
the passage of smoke and fire. Openings through fire-resistance-
rated assemblies shall be protected by self-closing or automatic-
closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barrier partitions
shall be maintained to prevent the passage of smoke and all
openings protected with approved smoke barrier doors or
leakage-rated (smoke) dampers.
703.2 Opening protectives. Opening protectives shall be
maintained in an operative condition in accordance with NFPA
80. Fire doors and smoke barrier doors shall not be blocked or
obstructed or otherwise made inoperable. Fusible links shall be
replaced promptly whenever fused or damaged. Fire door assemblies
shall not be modified.
10/09/2007 INSP - FULL Violation 1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise’s electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate the following areas:
1. Exit access corridors, passageways and aisles in rooms
and spaces which require two or more means of egress.
2. Exit access corridors and exit stairways located in buildings
required to have two or more exits.
3. Exterior egress components at other than the level of exit
discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section
1023.1, in buildings required to have two or more exits.
5. The portion of the exterior exit discharge immediately
adjacent to exit discharge doorways in buildings required
to have two or more exits.
The emergency power system shall provide power for a duration
of not less than 90 minutes and shall consist of storage
batteries, unit equipment or an on-site generator. The installation
of the emergency power system shall be in accordance with
Section 2702.
10/09/2007 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adaptors, such as cube
adaptors, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed.
605.4.2 Power supply. Relocatable power taps shall be directly
connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor cover-
10/09/2007 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space. 30 inches wide.
10/09/2007 INSP - FULL Violation