Case: T07FR01990

Parcel: 14108521C

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
11/06/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
10/30/2007 VIOL - BUILDING SVCS & SYSTEMS Compliance Items removed, tap plugged into outlet, extension cord removed, junction boxes covered
10/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches, the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
· Remove items from area (north and south walls)
10/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
· Plug tap directly into receptacle
10/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
· Remove extension cord from coffee pot
10/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
· Replace covers on boxes (south, north, and east walls)