Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR01917

Parcel: 106100160


Addresses:

1870 W PRINCE RD


Inspection Status: Approved

Inspection History: INSP - SELF INSPECTION PROGRAM

Case Number - T07FR01917

Inspection Description - INSP - SELF INSPECTION PROGRAM

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2007 INSP - SELF INSPECTION PROGRAM Approved abated
10/22/2007 INSP - SELF INSPECTION PROGRAM Correction Required items #3, 5 abated.

req'd still: unapproved extension cord use, flam liquid quantities

er-inspection Nov. 5, 2007
10/02/2007 INSP - SELF INSPECTION PROGRAM Correction Required correction req'd by Oct 16, 2007

Item#3, 5, 11, 14
10/01/2007 INSP - SELF INSPECTION PROGRAM Correction Required 1. IFC 505.1: Is the address clearly visible from the street? Y

2. IFC 901.6: Is there an extinguisher (75 feet)? Y

3. IFC 901.7: Is the fire extinguisher mounted properly? N

4. IFC 901.6: ...Serviced within the last year? Y

5. IFC 1008.1.8.3: "Door to Remain Unlocked" sign posted? N

6. IFC 10011.1: Are exits identified with EXIT signs? N

7. IFC 1027.2: Is the exit clear of obstructions? Y

8. IFC 605.3: Proper electrical panels clearance? Y

9. IFC 315.2.1: Stored materials two feet below the ceiling? Y

10. IFC 1026.3: Does emergency lighting work? NA

11. IFC 605.5: Extension cords used only temporary? N

12. IFC 605.1: Outlets have no more than two items plugged in? N

13. IFC 605.6: Are all switches/outlets equipped with covers? (unknown, illegibly marked on form)

14. IFC 3404.3.4.2 #2: Less than 10 gal of flammable liquid? N

15. IFC 901.6: Sprinkler system been tested within 12 mos? NA

16. IFC 901.6: Fire alarm system been tested within 12 mos? NA

17. IFC 305.1: Heat-producing appliances clear of combustibles? Y

PERSON NAME: Roger Hanft
BUSINESS NAME: SoundSpeakerDesign.com
PHONE: 888-2501