Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Approved. | |
| 01/25/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ACH cannnot find a company to make repairs. Cintas and Wildcat fire have seen the work and have not sent in bids. will furnish additional company info. to manager. | |
| 11/28/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ALL O.K. 11/28, with the exception of sprinkler coverage violation. Contact will continue to try to find company to extend coverage, I provided Mr. Deal with a list of sprinkler contractors. Will re-contact w/in two weeks from today. | |
| 10/09/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____No sprinkler coverage in conference room. 2006 IFC 901.4 ***Extend sprinkler coverage to conference room. |
|
| 09/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____All fire extinguishers need annual inspection, and inspection tag. 2006 IFC 901.6 ***Have ALL extinguishers inspected, tagged. |
|
| 09/27/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Sprinkler system inspection tag missing, needs test, or if current, inspection tag. 2006 IFC 901.6.2 |