Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01871
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ALL O.K. 11/28. | |
09/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Fire department connections (FDC's) blocked by storage, carts. IFC 912.3 ***Unblock access to FDC's to ensure identification and access. |
|
09/25/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | ____Sprinkler head dirty, lint buildup. (Meat cooler) 2006 IFC 901.6 ***Clean sprinkler head. |