Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2007 | VIOL - MEANS OF EGRESS | Approved | All O.K 10/26. | |
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Double keyed locks in use. -kitchen to courtyard. -kitchen to rear parking lot. 2006 IFC 1008.1.8 ***Remove double keyed locks, replace with thumblatch lock. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Exit signs out of service. -hallway to kitchen. -south sleeping porch. -main entrance. -west hallway, 2nd floor. 2006 IFC 1028.4 ***Repair signs to working order. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Blocked exits. 2006 IFC 1003.6 ***Corrected in my presence. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Storage in exit pathway. -In dorm hallways. -basement exit stairs.(dungeon) 2006 IFC 1003.6 ***Unblock hallways and stairways, keep clear at ALL times. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Emergency lighting out of service. -2nd floor adjacent to room 19. 2006 IFC 1027.5 ***Repair lighting to working order. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Mirror installed on exit door. -1st floor hallway. 2006 IFC 1008.1 ***Remove mirror from exit door. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Exit door out of adjustment, does not move freely. -basement. (dungeon) 2006 IFC 1008.1.2 ***Repair exit door to move freely, initiating force to be 15lbs. pushing pressure or less. |
|
| 10/02/2007 | VIOL - MEANS OF EGRESS | Correction Required | ____Exit stairway handrail is damaged. -east exit stairway. 2006 IFC 1012.4 ***Repair handrail to allow support the full lenth of stairway. |