Case: T07FR01827

Parcel: 14108521C

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/11/2007 VIOL - BUILDING SVCS & SYSTEMS Approved panel cleared
09/20/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

ยท Clear the space around the electrical panel in the computer room.